MIST SEPARATOR

Mist Separator Sizing For Low Pressure Boilers


LBS. PER HOUR OF STEAM
MODEL
500#/hr.
1,000#/hr.
1,500#/hr.
2,500#/hr.
5,000#/hr.
7,500#/hr.
10,000#/hr.
5 psig
MSI
3"-8"-38"
5"-10"-46"
6"-14"-50"
6"-18"-58"
8"-24"-70"
8"-30"-78"
10"-36"-90"
MBI
3"-8"-26"
5"-10"-30"
6"-14"-34"
6"-18"-38"
8"-30"-52"
8"-30"-52"
10"-36"-58"
MTI
3"-8"-32"
5"-10"-40"
6"-16"-48"
6"-18"-52"
8"-30"-74"
8"-30"-74"
10"-36"-84"
10 psig
MSI
3"-8"-38"
5"-10"-46"
6"-12"-50"
6"-16"-58"
8"-24"-70"
8"-30"-78"
10"-30"-84"
MBI
3"-8"-26"
5"-10"-30"
6"-12"-32"
6"-16"-36"
8"-24"-44"
8"-30"-52"
10"-30"-52"
MTI
3"-8"-32"
5"-12"-40"
6"-14"-44"
6"-16"-48"
8"-24"-64"
8"-30"-74"
10"-30"-76"
12 psig
MSI
3"-6"-34"
5"-10"-48"
6"-12"-50"
6"-14"-50"
8"-20"-64"
8"-30"-78"
10"-30"-84"
MBI
3"-6"-24"
5"-10"-30"
6"-12"-32"
6"-14"-34"
8"-24"-44"
8"-30"-52"
10"-30"-52"
MTI
3"-8"-32"
5"-12"-40"
6"-14"-44"
6"-16"-48"
8"-24"-64"
8"-30"-74"
10"-30"-76"

Model No. "Inlet Size-Diameter-Height". Other sizes are available in our Complete Catalog.


Mist Separator Sizing Other Applications

The proper selection of a Mist Separator for your specific application can best be obtained by presenting detailed information to Penn Separator. Include the following information where possible. With this information Penn can offer a proposal on a separator for your specific needs.

1. Flow Rate 5. Liquid Partical Size.
2. Vapor Density. 6. Process and System Description.
3. Liquid Density. 7. Operating Pressure and Temperature.
4. Liquid Viscosity 8. Line Size Horizontal or Vertical.


Suggested Specifications

Furnish and install as shown on plans a Mist Separator Syle MTI, MSI, or MBI constructed of Carbon or Stainess Steel built according to ASME Code for 150 psig @ 450 deg. F. or _________ psig as required for the application. The mist separator will include a fine wire 304 stainless steel mist eliminator element centrally located and selected to provide a 99+% efficiency for entrained liquids 10 micron size and larger witha pressure drop not exceeding 3" of water.

The separator is to include a 150# Flanged inlet and outlet _________" size to match the line size. Couplings are included for the entrainment drain, inspection ports, and element backwash connection. The exterior of the unit includes a coat of shop primer.


PENN SEPARATOR CORPORATION
5 South Pickering
P.O. BOX 340
Brookville, PA 15825
(814) 849-7328
Fax: (814) 849-4510
TOLL FREE: 1-888-PENN-SEP (7366-737)