1.
Calculate the Cu. Ft. amount of blowoff when lowering the
Boiler Water Level 4". The following formula should be
used: Cu. Ft. of Blowoff = 4"/12" X Drum Dia. Ft.
X Drum Length Ft.
2.
Select a Blowoff Tank which has Cu. Ft. holding capacity equal
to the amount calculated.If the amount of Blowoff is known
select a tank with that amount holding capacity.
3.
Select the drain and vent nozzles below using the Blowdown
Valve Size and Boiler Operating Pressure.The inlet should
be the same size as the Blowoff Valve. |